Select Your Region

Asia/Pacific
中国 India Việt nam 대한민국 Australia
Europe
Türkiye United Kingdom France Deutschland Nederland España Polska Україна Italia Sverige
North America
United States México
South America
Brasil
Africa
South Africa
Global language
Global language

Reliability    Safety    Capacity

S5-GC(100-125)K

400V: 100K/110K;   480V: 125K-HV

S5-GC(100-125)K three phase series string inverter adopt 10 MPPT design to provide a more flexible configuration scheme with a smaller environmental impact rate and higher generation efficiency. Anti-resonance, supporting over 6MW parallelled in one transformer, Strings intelligent monitoring, Smart I-V Curve Diagnosis supported

100-125kW Three Phase Inverter

Leading Features

  • > 150% DC/AC ratio

  • Night SVG function
  • Type I SPD for AC (optional)
  • 10 MPPTs, max. efficiency 99.0%
  • High power tracking density 90MPPT/MW
  • Power line communication (PLC) (optional)
  • Support "Y" type connection in DC side
  • Remote firmware upgrade with simple operation
  • AFCI protection, proactively reduces fire risk
  • Supports aluminium wire access to reduce cost
  • Intelligent string monitoring. Smart I-V curve scan
  • Globally recognised branded componentry for longer life
  • Built-in PID recovery for better module performance (optional)
  • String current up to 16A, perfectly match large current / bificial modules
  • Overvoltage load reduction and leakage current suppression technology, low failure rate

Technical Specifications

Input DC

  • Rated voltage
    600 V
  • Start-up voltage
    195 V
  • MPPT voltage range
    180-1000 V
  • Max. input current
    10*32 A
  • Max. short circuit current
    10*50 A
  • MPPT number
    10
  • Max. input strings number
    20

Output AC

  • Max. apparent output power
    110 kVA
  • Max. output power
    110 kW
  • Rated grid voltage
    3/N/PE, 220 V / 380 V, 230 V / 400 V
  • Rated grid frequency
    50 Hz / 60 Hz
  • Rated grid output current
    152.0 A / 144.3 A
  • Max. output current
    167.1 A
  • Power Factor
    >0.99 (0.8 leading - 0.8 lagging)
  • THDi
    <3%

Efficiency

  • EU efficiency
    98.3%

Protection

  • Short circuit protection
    Yes
  • Output over current protection
    Yes
  • Surge protection
    DC Type II / AC Type II (AC Type I optional)
  • Grid monitoring
    Yes
  • Anti-islanding protection
    Yes
  • Strings monitoring
    Yes
  • I/V Curve scanning
    Yes
  • Integrated PID recovery
    Optional
  • Integrated AFCI (DC arc-fault circuit protection)
    Yes
  • Integrated DC switch
    Yes
  • Integrated AC switch
    Optional

General Data

  • Weight
    91 kg
  • Topology
    Transformerless
  • Self consumption (night)
    <2 W
  • Operating ambient temperature range
    -25~60℃
  • Relative humidity
    0~100%
  • Ingress protection
    Ip66
  • Cooling concept
    Intelligent redundant fan-cooling
  • Max.operation altitude
    4000 m
  • Safty/EMC standard
    IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4
  • Grid connection standard
    VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1, UTE C15-712-1, NRS 097-1-2, G98, G99, EN 50549-1/-2, RD 1699, UNE 206006, UNE 206007-1, IEC61727,DEWA

Features

  • AC connection
    OT terminal (max. 185 mm²)
  • Display
    LCD
  • Communication
    RS485, Optional: Wi-Fi, GPRS, PLC

Sales Enquiries: sales@ginlong.com
Copyright@2019 Ginlong Technologies All rights reserved